OCPP 1.6J central system that keeps building base load plus all EV chargers under the main fuse: phase aware, fair sharing, fault tested. Simulated building.

Topics

Resources

Stars

0 stars

Watchers

0 watching

Forks

Latest commit

 

History

3 Commits

Folders and files

Repository files navigation

ocpp-load-managed-charging

EV charging in an apartment building without upgrading the grid connection: an OCPP 1.6J central system that keeps the flats plus every charger under the main fuse, phase by phase, and shares the rest fairly. Real protocol, simulated building and cars.

Result: no load management vs static split vs dynamic controller

What it does

  • OCPP 1.6J central system (Python, the MIT-licensed ocpp library, asyncio websockets, subprotocol ocpp1.6). It receives BootNotification, StatusNotification, StartTransaction/StopTransaction and MeterValues (Current.Import per phase L1-L3, energy register).
  • Every minute it sends each active session a SetChargingProfile (TxProfile, absolute, limit in A per phase). After every boot it sends a TxDefaultProfile with a 6 A failsafe limit, so a new or offline session starts low.
  • Fuse rule: building base load + all chargers <= main fuse (default 3x63 A, configurable, e.g. --fuse 80) minus a 3 A margin, on each phase separately. Base load = building meter minus the currents of the sessions under control.
  • Phase aware: chargers are installed with rotated phases; a single-phase car is detected from its per-phase MeterValues and only counts on its phase. Until detected, a car counts on all three.
  • Minimum current: a car gets 6 A or more, or it is paused (limit 0 A). Paused cars take over from running ones only every 15 minutes (no flapping).
  • Fair sharing, three policies: equal share (max-min fair water filling), first come, departure aware (cars that must leave soon get the current they need first). Departure time and energy wish come from the resident over OCPP DataTransfer (stands in for an app).
  • Failure handling: an offline charger keeps its last limit reserved; a stale meter switches to an assumed worst-case base load (55 A); a charger that draws more than its limit (+1.5 A) is flagged and its full rating is reserved.
  • Comparison on the same simulated weeks: no load management, static equal split (fixed 45 A reserve for the flats, no meter), the dynamic controller, and an ablation that only checks the total kW budget (not phase aware).

Results

Simulated building: 24 flats with a heat pump, 12 chargers (11 kW, a third of the cars charge on one phase), seeded base load and car sessions, 8 representative weeks (two each in January, April, July, October), one-minute steps. 316 sessions, 4.28 MWh requested. "Above the fuse" = one-minute mean current on any phase above the rating. All numbers come from python -m olmc demo (results/summary.md, results/metrics.json).

12 chargers, 3x63 A (main case)

Strategy Minutes above fuse Max phase current Peak building power Energy delivered by departure Worst session Worst car Jain index (sessions) Pauses per session
No load management 3038 124.5 A 74.9 kW 100 % 100 % 100 % 1.000 0
Static equal split 27 69.1 A 43.8 kW 98.46 % 60.3 % 93.4 % 0.998 2.3
Dynamic, equal share 0 61.8 A 41.9 kW 99.96 % 96.5 % 99.7 % 1.000 0.21
Dynamic, first come 0 62.0 A 41.9 kW 99.93 % 93.5 % 99.4 % 1.000 0.16
Dynamic, departure aware 0 61.8 A 41.9 kW 100 % 100 % 100 % 1.000 0.20
Dynamic, kW budget only (not phase aware) 3356 86.1 A 42.5 kW 100 % 100 % 100 % 1.000 0.04
  • The kW-only controller keeps total power right but overloads single phases: more minutes above the fuse than no control at all. Phase awareness is not optional.
  • The dynamic controller leaves a short overshoot after sudden base-load steps until the cars follow (10 s modelled): 3820 s in 8 weeks, never long enough to lift a one-minute mean above 63 A.
  • Controller decision time (pure Python, 4-core laptop shared with other jobs): median 29 us, 99th percentile 300 us per cycle.

Sensitivity

Case Strategy Minutes above fuse Energy delivered Worst session
12 chargers, 3x80 A no load management 1143 100 % 100 %
static equal split 1 99.94 % 94.3 %
dynamic, departure aware 0 100 % 100 %
24 chargers (every flat), 3x63 A, 629 sessions no load management 8786 100 % 100 %
static equal split 27 83.93 % 21.7 %
dynamic, equal share 0 99.59 % 66.4 %
dynamic, departure aware 0 99.84 % 84.7 %

Closed loop over real OCPP websockets (localhost, 12 simulated chargers, departure-aware policy, 24 virtual hours from 12:00 on a January weekday, 9 sessions):

Run Minutes above fuse Max phase current Energy delivered Profiles sent / accepted MeterValues Cycle time p50 / p95 / max What the controller logged
No fault 0 60.9 A 100.0 % 2243 / 2243 7592 15.1 / 34.5 / 62.7 ms -
CP01 websocket lost 19:00-20:00 0 60.9 A 100.0 % 2184 / 2184 7532 15.9 / 33.8 / 78.8 ms t+420 min CP01: offline; t+480 min CP01: back online
Meter frozen 19:00-20:00 0 61.2 A 100.0 % 2636 / 2636 7592 17.2 / 34.8 / 92.1 ms t+422 min meter: stale
CP02 accepts profiles but ignores them 0 61.1 A 100.0 % 2074 / 2074 7592 21.9 / 33.6 / 62.2 ms t+250 min CP02: ignores profile

Cycle time = meter read, decision, SetChargingProfile to every active session (up to 9 at once) and all replies received, on localhost. The non-compliant charger was flagged in its first cycle (it drew 16 A against the 6 A default profile) and its full 16 A was reserved from then on.

Quick start

uv venv .venv --python 3.12
uv pip install --python .venv/Scripts/python.exe -e ".[dev]"   # Linux/macOS: .venv/bin/python
.venv/Scripts/python.exe -m olmc demo          # ~6 min: 8 weeks x strategies + 4 OCPP runs; writes results/ and docs/
.venv/Scripts/python.exe -m olmc demo --quick  # one week + the OCPP runs (what CI runs)
.venv/Scripts/python.exe -m olmc live --fuse 80 --ignore CP05   # one closed-loop day, prints a JSON summary
.venv/Scripts/python.exe -m pytest -q -p no:asyncio && .venv/Scripts/ruff.exe check .

How it works

flowchart LR
  M[Building meter: total A per phase] --> C[Controller]
  CP[Chargers 1..12] -- OCPP MeterValues, DataTransfer --> CS[OCPP 1.6J central system]
  CS --> C
  C -- limits A per phase --> CS
  CS -- SetChargingProfile TxProfile --> CP
Loading
  • olmc/allocate.py: pure allocation. Admission in priority order at 6 A, then max-min fair water filling over coupled phases (or first come / departure need first). Limits are rounded down to 0.1 A, so the sum per phase never exceeds what is free.
  • olmc/controller.py: one cycle, no I/O: headroom per phase from the meter, reserves for offline and non-compliant chargers, stale-meter fallback, phase detection, rotation.
  • olmc/csms.py, olmc/chargepoint.py: OCPP 1.6J central system and simulated charger (obeys TxDefaultProfile and TxProfile; can be made to ignore them).
  • olmc/sim.py: minute simulation. Inside each minute the base load steps, the cars keep their old limits for 10 s (control cycle + charger and car response, assumed), then follow the new ones.
  • olmc/live.py: the same loop over websockets with fault injection. olmc/data.py: the simulated building.

Data sources

All data is simulated and seeded (seed=7), no measured data:

  • Base load: 24 flats (fridge and standby, lights, kettle, hob on two phases, oven, dishwasher), a shared laundry room, lift and ventilation, and a modulating heat pump driven by a simulated seasonal temperature. About 64 MWh per year, highest phase 61 A.
  • Cars: one per charger, commuter / home-office / retired driving profiles, 0.19 kWh/km (+20 % in winter), plug-in most evenings. The request is capped at what the car could take at full power while plugged in, so 100 % is reachable without a fuse.

What is not verified yet

  • Never run against real chargers, real cars or a real building meter. Only the simulated chargers in this repo spoke OCPP to it; no third-party charger was tested.
  • Car behaviour is modelled: constant current up to the limit, no taper near full, instant pause below 6 A, no car that refuses to resume after a pause.
  • The 10 s reaction time is assumed, not measured. Real meters, chargers and cars add their own delays.
  • The fuse check uses one-minute means; fuse trip curves and sub-minute load peaks are not modelled.
  • Departure time and energy wish come over a DataTransfer message as a stand-in for a residents' app; no app exists.
  • One simulated building, one seed, 8 weeks.

Licence

MIT, Copyright (c) 2026 VB-Builds. Dependencies: ocpp (MIT), websockets (BSD-3-Clause), numpy (BSD), matplotlib (matplotlib licence, BSD-style).