Add CV200 support and extend HRV156/HRV176 ventilation support - #3485

Merged
proddy merged 2 commits into
emsesp:devfrom
gereblye79:cv200-3.10.0-dev-9
Nov 27, 2026
Merged

proddy merged 2 commits into
emsesp:devfrom
gereblye79:cv200-3.10.0-dev-9

Conversation

@gereblye79

Copy link
Copy Markdown

CV200

  • Recognize the CV200 as a ventilation controller.
  • Publish controller date and time.
  • Correct an invalid or drifting controller clock using NTP.

HRV156/HRV176

  • Add writable nominal airflow in m³/h.
  • Add writable minimum outdoor temperature for bypass operation.
  • Add writable maximum supply air temperature for bypass operation.
  • Add automatic ventilation modes: auto L0-L4 and auto demand. Note: Settings written through EMS-ESP may subsequently be overwritten by the connected controller, as the controller continues to send its configured values.

Based on 3.10.0-dev-9a.

@proddy

proddy commented Nov 27, 2026

Copy link
Copy Markdown
Contributor

looks good. a few things:

  • set_airflowBalance is declared in ventilation.h and never defined/used. you can remove it.
  • 0x55C fetch length is still 2, you now read offsets 2 and 3 (bypassMinOutdoorTemp_, bypassMaxSupplyTemp_), but polling still requests only 2 bytes. Those entities won’t populate on a normal fetch. best to make it 4
  • the blower telegram 0x585 was replaced with 0x575, and offsets moved from 0/1 to 2/3. It could break other units that only broadcast on 0x585. Confirm both types aren’t needed (or handle both), and mention the speed-value meaning change in the changelog.
  • new uint members aren’t initialized to EMS_VALUE_*_NOTSET
  • autoL0 shortname is "autooff", best to keep it autoL0 so its consistent with the rest

@proddy
proddy merged commit 19f154d into emsesp:dev Nov 27, 2026
@gereblye79

Copy link
Copy Markdown
Author

looks good. a few things:

* set_airflowBalance is declared in ventilation.h and never defined/used. you can remove it.

* 0x55C fetch length is still 2, you now read offsets 2 and 3 (bypassMinOutdoorTemp_, bypassMaxSupplyTemp_), but polling still requests only 2 bytes. Those entities won’t populate on a normal fetch. best to make it 4

* the blower telegram 0x585 was replaced with 0x575, and offsets moved from 0/1 to 2/3. It could break other units that only broadcast on 0x585. Confirm both types aren’t needed (or handle both), and mention the speed-value meaning change in the changelog.

* new uint members aren’t initialized to EMS_VALUE_*_NOTSET

* autoL0 shortname is "autooff", best to keep it autoL0 so its consistent with the rest

Thanks for the detailed review. I've addressed the points and pushed the changes. I removed the unused declaration, increased the 0x55C fetch length to 4, initialized the new values to NOTSET, and renamed the autoL0 shortname for consistency.

For the blower telegram, I kept 0x585 with offsets 0/1 for compatibility. On my Bosch 5000c/MV200 I also observed 0x575 with the fan percentages at offsets 2/3, so I've documented that behavior in the code rather than replacing 0x585.

I also updated the changelog accordingly. Please take another look when you have a chance.